Sprinklers not Connected to the Sprinkler Piping System

Posted by Ron Brewer on Feb 12, 2019 12:17:46 PM

During the installation process, sprinklers are required to be inspected and pressure-tested as part of the commissioning phase. Subsequently, annual inspections and periodic testing, sometimes including line flushing is required.  Generally, these requirements are enough to ensure that a sprinkler system is installed correctly, and will perform its job when it is needed.

Recently, we ran into an unusual situation.  Some renovations were being done on a building, and when the building contractor opened up a hole in the floor, he noticed that there was what appeared to be a sprinkler pipe that was not connected to anything.  Upon investigation, it was determined that the pipe was the supply to a sprinkler in a stairwell – the sprinkler had been installed without being connected into the main sprinkler piping system!  Upon further investigation, a second disconnected sprinkler was also found in another stairwell. 

The building in question has over 500 sprinklers in it.  The owner asked our opinion on how to proceed.  In working with the building contractor and sprinkler contractor, we determined the following course of action.

  • One-by-one, the sprinkler lines were drained.
  • At the drain, a vacuum was connected to the sprinkler line, to put the system under negative pressure.
  • A sprinkler fitter then went to each sprinkler on the zone, and using a sprinkler wrench, cracked the sprinkler seal. It immediately became obvious whether the sprinkler was properly connected to the sprinkler piping system, as a suction noise was noted at the sprinkler.
  • The sprinkler was then replaced with a new sprinkler.

 During this process, we considered two questions.

  • Should we replace every sprinkler where the seal was cracked?
  • Should we test every sprinkler, or do a random selection?

stock-image-51500393

 

In answering the first question, NFPA 13 is very clear that sprinklers cannot be re-used. But was only cracking the seal to a sprinkler actually considered as re-using it?  Historical experience within our team was that the simple act of twisting a sprinkler to crack the seal can impact the sprinkler seat and cause it to leak.  In this occupied building, periodic leaks were not considered acceptable; we recommended replacing the sprinklers.

In answering the second question, we considered the fact that, along with other fire protection measures (such as building compartmentalization and the building alarm and detection system), the sprinkler system was an integral part of the holistic fire protection of the building.  It provides protection against fire spread, protection of egress paths, and is connected to the fire detection system.  If we missed any disconnected sprinklers, life safety in the building could be impacted. We recommended was that all sprinklers be tested.

Through this process, 2 additional sprinklers were found to not be connected into the sprinkler piping system.  The end result was a client who now has a restored faith in the sprinkler system in their building!

 

Contact Ron Brewer for a Free Consultation

Topics: Sprinkler System Design, NFPA 13, The Room Design Method, Sprinkler Piping System, Sprinkler System Inspections, Sprinkler Testing And Maintenance


Picture of Ron Brewer

Written by Ron Brewer

Mr. Brewer has a B.Sc. in Electrical Engineering from the University of Saskatchewan, and an MS in Fire Protection Engineering from the Worchester Polytechnic Institute. He is a registered professional engineer in Alberta, Ontario and British Columbia. Mr. Brewer has worked in the fire protection industry for over 30 years. He has considerable experience in the design, implementation, and commissioning of both fire alarm systems and special hazard suppression systems. He also has focused on code consulting, performance-based design, hazard assessment, and explosion protection. He has worked in industrial, commercial, healthcare, institutional, residential and nuclear industries. Mr. Brewer is currently involved with ULC working groups for fire alarm testing and verification (ULC-S536/537) and fire alarm control units (ULC-S527)

PLC Fire Safety Solutions consistently scores over 90% in our overall Client Satisfaction surveys.

News

04/03/2020
The Parallels Between Limiting Risk From Fire and COVID-19

One of the things that COVID-19 has made me realize is that the world is a small place. At the time...

Read More >>
04/23/2019
Applying the National Building Code to Historical Buildings Open to the Public

In the past few years, PLC Fire Safety Solutions have been involved in numerous fire and life...

Read More >>
03/15/2019
Fire Safety in Escape Rooms

“Escape Rooms” are businesses where a group of friends or co-workers pay a fee to be locked in a...

Read More >>
02/12/2019
Sprinklers not Connected to the Sprinkler Piping System

During the installation process, sprinklers are required to be inspected and pressure-tested as...

Read More >>
01/30/2019
The Room Design Method in NFPA 13

When I first started learning about sprinkler design, I was using the then current 1972 edition of...

Read More >>
Other articles